| Input Channels | 8 differential analog input channels (configurable for various signal types). | 
| Signal Compatibility | Supports 4–20 mA DC, 0–20 mA DC, 1–5 V DC, 0–10 V DC, and thermocouple/RTD inputs (e.g., J, K, T, R, S, Pt100). | 
| Accuracy | ±0.1% of full scale (for 4–20 mA and voltage signals); ±0.2°C (for RTDs); ±1°C (for thermocouples). | 
| Sampling Rate | Up to 10 samples per second per channel, ensuring real-time data acquisition. | 
| Isolation | Channel-to-channel isolation (2.5 kV AC) and galvanic isolation from the backplane, reducing noise interference. | 
| Power Requirements | Powered via the DeltaV system backplane; typical current draw: 120 mA at 5 V DC. | 
| Physical Dimensions | Compact design: approximately 120 mm × 80 mm × 30 mm (length × width × height), compatible with DeltaV rack enclosures. | 
| Environmental Adaptability | Operating temperature: 0°C to 60°C; storage temperature: -40°C to 85°C; relative humidity: 5% to 95% (non-condensing); compliant with industrial EMI/EMC standards. |